Correlation between stabilizer consumption and degree of polymerization of thermally upgraded paper aged in insulating natural ester and insulating mineral oil

Mildemberger, Larissa; Andreoli, Mario Carlos; Silva, Guilherme Cunha da; Motta, Heloisa Nunes da; Gulmine, Joseane Valente; Munaro, Marilda

Downloads: 0
Views: 962

Abstract

Insulating paper holds significant importance in the insulation system of power transformers, and thus, its degradation is the subject of many studies. A successful evaluation of the degradation rate of such paper contributes to reducing downtime and avoiding equipment failure. In this work, samples of thermally upgraded paper were thermally aged in insulating natural ester (INE) and insulating mineral oil (IMO) and were evaluated by degree of polymerization (DP) and FTIR-ATR. It was possible to identify characteristic bands of dicyandiamide, an inhibitory compound of the thermal degradation of the paper, and to establish a correlation between the decrease in DP and the consumption of dicyandiamide during aging, which was observed to develop in three distinct steps for both IMO and INE.

Keywords

thermally upgraded paper, thermal degradation, insulating natural ester, insulating mineral oil.

References

1. Fofana, I., Bouslimi, H., Hemmatjou, C., Volat, K., & Tahiri, K. (2014). Relationship between static electrification of transformer oils with turbidity and spectrophotometry measurements. International Journal of Electrical Power & Energy Systems, 54, 38-44. http://dx.doi.org/10.1016/j.ijepes.2013.06.037.

2. Prevost, T. A. (2005). Thermally upgraded insulation in transformer. In Proceedings of Electrical Insulation Conference and Electrical Manufacturing Expo (pp. 120-125). Indianapolis: IEEE.

3. Ciuriuc, A., Vihacencu, M. S., Dumitran, L. M., & Notingher, P. V. (2012). Comparative study on power transformers vegetable oil and mineral oil ageing. In Proceedings of International Conference on Applied and Theoretical Electricity (pp. 1-6). Craiova: IEEE.

4. Martins, M. A. G. (2007). Furfuraldeído: um indicador prático da degradação térmica do papel kraft de transformadores. Ciência e Tecnologia dos Materiais, 19(1-2), 25-33.

5. Liland, K. B., Ese, M. H. G., Selsbak, C. M., & Lundgaard, L. (2011). Ageing of oil impregnated thermally upgraded papers. In Proceedings of IEEE International Conference on Dielectric Liquids (pp. 1-5). Trondheim: IEEE.

6. Jalbert, J., Gilbert, R., Tétreault, P., Morin, B., & Lessard-Déziel, D. (2007). Identification of a chemical indicator of the rupture of 1,4-beta-glycosidic bonds of cellulose in an oil-impregnated insulating paper system. Cellulose, 14(4), 295-309. http://dx.doi.org/10.1007/s10570-007-9124-1.

7. Gilbert, R., Jalbert, J., Tétreault, P., Morin, B., & Denos, Y. (2009). Kinetics of the production of chain-end groups and methanol from the depolymerization of cellulose during the ageing of paper/oil systems. Part 1: standard wood kraft insulation. Cellulose, 16(2), 327-338. http://dx.doi.org/10.1007/s10570-008-9261-1.

8. Gilbert, R., Jalbert, J., Duchesne, S., Tetreault, P., Morin, B., & Denos, Y. (2010). Kinetics of the production of chain-end groups and methanol from the depolymerization of cellulose during the ageing of paper/oil systems. Part 2: thermally-upgraded insulating papers. Cellulose, 17(2), 253-269. http://dx.doi.org/10.1007/s10570-009-9365-2.

9. Setnescu, R., Badicu, L. V., Dumitran, L. M., Notingher, P. V., & Setnescu, T. (2014). Thermal lifetime of cellulose insulation material evaluated by an activation energy based method. Cellulose, 21(1), 823-833. http://dx.doi.org/10.1007/s10570-013-0087-0.

10. Martins, M. A. (2007). Monitorização da degradação térmica do papel isolante usado em transformadores: papel “thermally upgraded” versus papel kraft. Ciência e Tecnologia dos Materiais, 19(1-2), 14-18.

11. Prevost, T. A. (2009). Dielectric properties of natural esters and their influence on transformer insulation system design and performance: an update. In Proceedings of Power & Energy Society General Meeting (pp. 1-7), Calgary: IEEE.

12. McShane, C. P., Rapp, K. J., Corkran, J. L., Gauger, G. A., & Luksich, J. (2001). Aging of paper insulation in natural ester dielectric fluid. In Proceedings of Transmission and Distribution Conference and Exposition (Vol. 2, pp. 675-679). Atlanta: IEEE.

13. Yang, L., Liao, R., Caixin, S., & Zhu, M. (2011). Influence of vegetable oil on the thermal aging of transformer paper and its mechanism. IEEE Transactions on Dielectrics and Electrical Insulation, 18(3), 692-700. http://dx.doi.org/10.1109/TDEI.2011.5931054.

14. Frimpong, G. K., Oommen, T. V., & Asano, R. (2011). A survey of aging characteristics of cellulose insulation in natural ester and mineral oil. IEEE Electrical Insulation Magazine, 27(5), 36-48. http://dx.doi.org/10.1109/MEI.2011.6025367.

15. Associação Brasileira de Normas Técnicas – ABNT. (2009). ABNT NBR IEC 60450: medição do grau de polimerização viscosimétrico médio de materiais celulósicos novos e envelhecidos para isolação elétrica. Rio de Janeiro.

16. Shroff, D. H., & Stannett, A. W. (1985). A review of paper aging in power transformers. IEE Proceedings. Part C. Generation, Transmission and Distribution, 132(6), 312-319. http://dx.doi.org/10.1049/ip-c.1985.0052.

17. Yu, X., Tong, S., Ge, M., Wu, L., Zuo, J., Cao, C., & Song, W. (2013). Synthesis and characterization of multi-amino-functionalized cellulose for arsenic adsorption. Carbohydrate Polymers, 92(1), 380-387. http://dx.doi.org/10.1016/j.carbpol.2012.09.050. PMid:23218309.

18. Urreaga, J. M., & Orden, M. U. (2007). Modification of cellulose with amino compounds: a fluorescence study. Carbohydrate Polymers, 69(1), 14-19. http://dx.doi.org/10.1016/j.carbpol.2006.08.019.

19. Morais, R. M., Mannheimer, W. A., Carballeira, M., & Noualhaguet, J. C. (1999). Furfural analysis for assessing degradation of thermally upgraded papers in transformer insulation. IEEE Transactions on Dielectrics and Electrical Insulation, 6(2), 159-163. http://dx.doi.org/10.1109/94.765905.

20. Yang, L., Liao, R., Sun, C., & Sun, H. (2008). Study on the influence of natural ester on thermal ageing characteristics of oil-paper in power transformer. In Proceedings of International Conference on High Voltage Engineering and Application (pp. 437-440). Chongqing: IEEE.

21. Lundgaard, L. E., Hansen, W., Linhjell, D., & Painter, T. J. (2004). Aging of oil-impregnated paper in power transformers. IEEE Transactions on Power Delivery, 19(1), 230-239. http://dx.doi.org/10.1109/TPWRD.2003.820175.